Transformer Working Principle: How the Primary Knows the Load

In the transformer working principle, secondary load current opposes the core flux, so the primary draws more current. Distribution transformers of 63 kVA and above pass about 98 to 99% of power.

By Rahul Jeewani, Founder · Updated 15 Nov 2026

A grey pole-mounted distribution transformer above a quiet Indian residential street at dusk, with cables running to nearby houses.

Key takeaways

  • The primary draws more current under load because secondary current weakens the core flux, the voltage the primary induces against the supply dips, and primary current rises until the ampere-turns (current multiplied by turns) of both windings cancel. In the ideal case that is Ip·Np = Is·Ns (Wikipedia, Transformer).

  • The supply voltage fixes the core flux through the equation Erms ≈ 4.44 f N A Bpeak, where Erms is the root-mean-square (RMS) value of the induced EMF (electromotive force, the induced voltage) (Wikipedia, Transformer). So flux barely changes whatever the load.

  • In a 2015 BEE list, among the 348 rows for 100 kVA units that we could extract, full-load loss runs from 945 to 1,800 W, which is 98.23% to 99.06% efficiency by our calculation (BEE star rating list). The 98 to 99% range holds for units of about 63 kVA and above; the 25 kVA units fall below it.

  • Run four checks before you write a transformer answer: ratio direction (Vp·Ip = Vs·Is for an ideal unit), ideal versus real (use η = Pout/Pin with losses when the question gives them), load change (find Is first, then Ip = Is·Ns/Np), and sanity (η below 100%, about 98 to 99% for a large unit).
In this article
  1. 1What is the transformer working principle, in four steps?
  2. 2How does the primary know when you connect a load to the secondary?
  3. 3How far is a real transformer from the ideal one?
  4. 4How do you check a transformer numerical before you write the answer?
  5. 5How do we teach this at RG Lectures?
  6. 6Frequently asked questions

Most textbook treatments of the transformer state mutual induction, then jump to Vs/Vp = Ns/Np. A question many students ask is left open. Nothing but a magnetic field joins the two coils, so how does the primary know you connected a heavier load?

The answer rests on one fact: the supply voltage, not the load, fixes the flux in the core. Once that clicks, the rise in primary current, the puzzle of why the net flux is not zero, and the inverse current ratio stop being separate things to memorise.

The textbook "ideal transformer" also loses nothing, and no working one behaves that way. We counted the loss figures for 100 kVA (kilovolt-ampere, the power rating) distribution transformers, the units that bring supply voltage down for local use, to see how big the gap is.

Below you get the principle in four steps, how the primary senses a load, the real loss data, and a four-check routine you can run on any transformer numerical before you write the answer.

What is the transformer working principle, in four steps?

The transformer working principle is mutual induction: a changing current in the primary winding changes the magnetic flux in the iron core, and that changing flux induces a voltage in the secondary winding. The primary winding is the coil connected to the supply, and the secondary winding is the coil connected to the load. Flux is the magnetic field passing through a coil. EMF (electromotive force) is the voltage induced by changing flux. Inside, a laminated core carries the two windings, the primary and the secondary.

  1. An alternating supply drives alternating current through the primary winding.
  2. That current sets up an alternating flux in the core.
  3. The core guides the flux through the secondary winding, so the same flux links both coils.
  4. By Faraday's law (a changing flux through a coil induces an EMF in it), the changing flux induces an EMF in every turn of both windings, so the secondary voltage depends on its number of turns.

The result is the turns-ratio relation: the ratio of secondary to primary voltage equals the ratio of the number of loops in their coils (OpenStax College Physics, 2012), Vs/Vp = Ns/Np. The induction law behind step 4 is the one we work through in our Faraday's Law numericals page.

A steady direct current makes a steady flux, and a steady flux induces nothing. That is why a transformer needs alternating current.

How does the primary know when you connect a load to the secondary?

The primary senses the load through the core flux: current in the secondary produces a flux that opposes the core flux, the primary's back EMF dips, and the supply pushes extra current into the primary until the balance is restored. No signal passes between the coils, only the shared flux.

Here is the sequence, state by state.

The supply fixes the flux. The changing flux induces a back EMF in the primary winding (the voltage that opposes the supply). That back EMF almost equals the supply voltage Vp. The EMF equation Erms ≈ 4.44 f N A Bpeak (Wikipedia, Transformer) links the root-mean-square (RMS) EMF to frequency f, turns N, core area A and peak flux density Bpeak. The load does not appear in it. With Vp, f and the primary turns fixed, the peak flux is fixed.

A cutaway transformer with two coils and blue flux loops in the iron core, a fan switched on at the secondary side and thicker current flowing into the primary.
The load current's opposing flux is what makes the supply push more current into the primary.
StateSecondary currentCore fluxPrimary current
Secondary openZeroSet by Vp, f and primary turnsSmall magnetising current only (the primary current that sets up the core flux)
Load connectedIs, set by the loadStill set by the supply, so nearly unchangedMagnetising current plus the load part, Is·Ns/Np

Closing the secondary. Current Is flows. By Lenz's law (an induced current always opposes the change that causes it) its flux opposes the core flux. The core flux dips fractionally, the back EMF falls just below Vp, and the difference drives more current into the primary. That extra current grows until its ampere-turns cancel the secondary's: Ip·Np = Is·Ns in the ideal case, written in the source as ip·np − is·ns = 0 (Wikipedia, Transformer).

Why the net flux is not zero. Only the load part of the primary current is cancelled. The magnetising current has no partner in the secondary, so it keeps the flux at the value the supply demands. In a real unit a little flux leaks (leakage flux, which links only one winding), so the cancellation is slightly imperfect.

In an exam, write it as a chain: load current in the secondary, flux opposed, back EMF falls, primary current rises, ampere-turns balance.

How far is a real transformer from the ideal one?

A real 100 kVA distribution transformer loses 945 to 1,800 W at full load in a 2015 BEE list of approved units, so its efficiency works out to 98.23% to 99.06% at unity power factor (current and voltage in step). The ideal transformer of the textbook sits at exactly 100%, and the real ones sit just under it.

We took the Bureau of Energy Efficiency's star rating list for distribution transformers (71 pages, printed 14 September 2015, hosted on the Kerala government's energy site). In November 2026 we extracted its text and read the 1,388 rows our parser could capture. Each row is one brand-and-model approval, not one manufacturer, and gives total loss in watts at 50% and 100% loading. We kept the 100% loading column.

We then worked out efficiency as η = 100,000 / (100,000 + loss) for the 100 kVA rows, and the equivalent for other ratings. This is our model and assumes unity power factor and rated kVA delivered.

RatingRows extractedTotal loss at 100% loadingEfficiency (our calculation)
25 kVA372380 to 695 W97.30% to 98.50%
63 kVA312708 to 1,250 W98.05% to 98.89%
100 kVA348945 to 1,800 W98.23% to 99.06%
200 kVA891,659 to 2,700 W98.67% to 99.18%

Among the 100 kVA rows, 262 of 348 (75%) sit at exactly 1,800 W. The efficiency range rises with rating, as distribution transformers' efficiency of about 98 to 99 percent, improving with capacity leads you to expect. OpenStax puts efficiency of transformers "often" above 99%, which the larger units in the table match. The 98 to 99% figure holds for units of about 63 kVA and above; the 25 kVA rows fall below it, at 97.30% to 98.50%.

Two limits apply. The list holds approvals dated 2012 to 2015, so it is a snapshot of that period, not today's market. And we have not tied any row to a star level, so the table says nothing about star ratings.

For your answers: where a question says "assume an ideal transformer", use Pin = Pout. Where it gives a loss, copper loss, or efficiency, do not. A loss of 1,800 W is heat produced at 1.8 kW whenever the unit runs at full load.

How do you check a transformer numerical before you write the answer?

Run four checks, each with a pass or fail you can see on your paper. They catch the usual slips: a flipped ratio, an ignored loss, a changed load and an efficiency above 100%. For the general method behind them, see how to solve physics numericals in four steps.

A student at a desk checking a physics problem on paper with a pencil and calculator in a bright study room.
Checking each answer against the ratio, losses and efficiency limit catches the usual slips before you commit.
  1. 1
    Ratio direction
    Vs/Vp = Ns/Np and Is/Ip = Np/Ns. Pass: Vp·Ip equals Vs·Is for an ideal transformer. Fail: the two products differ, so you flipped a ratio. A step-up transformer (Ns > Np) must give Is < Ip.
  2. 2
    Ideal or real
    If the question mentions loss, heating or efficiency, use η = Pout / Pin (efficiency is output power divided by input power) with Pin = Pout + losses. Pass: your Pin is larger than your Pout. Fail: you equated Vp·Ip and Vs·Is in a question that gave a loss.
  3. 3
    Load change
    If the question adds or removes a load, find Is first (Is = Vs/R for a resistive load), then Ip = Is·Ns/Np. Pass: Vs stayed at the turns-ratio value. Fail: you changed Vp or Vs.
  4. 4
    Sanity
    Pass: η is below 100%, and for a large unit it is around 98 to 99%. Fail: η is 100% or above.

Worked example (our illustration). Take a single-phase 100 kVA transformer, 2,200 V primary and 220 V secondary, at full load and unity power factor. The voltages are our choice and not taken from the BEE list. We borrow only its loss figures and treat them as full-load losses.

  • Ratio: Ns/Np = 220/2,200 = 1/10, a step-down. Is = 100,000/220 = 454.5 A, so Ip = 454.5 × 1/10 = 45.45 A. Check: 2,200 × 45.45 = 100,000 W, which equals Vs·Is, so it passes.
  • Slip: multiplying by 10 instead gives 4,545 A and Vp·Ip = 10,000,000 W, which fails check 1.
  • With losses, Ip = Pin/Vp:
CasePinPrimary current
Ideal100,000 W45.45 A
Loss 945 W (lowest 100 kVA row)100,945 W45.88 A
Loss 1,800 W (commonest row)101,800 W46.27 A

So the primary current rises by about 0.9% and 1.8% over the ideal figure. That is small enough that "ideal" gives a good estimate and large enough that a question quoting a loss expects you to use it.

How do we teach this at RG Lectures?

At RG Lectures, Rahul Jewaani (RG Sir) teaches physics in our live batches, and we have been doing it since May 2018. Padhna Aasaan Hai: the transformer is a good example, because one fixed idea (flux set by the supply) explains three things students usually memorise.

The MHTCET 2027 Long Term Batch covers MHT-CET (Maharashtra Health and Technical Common Entrance Test) Physics and Chemistry, with live classes, recordings, and Class 11 Physics basics. See the course page for the current fee.

Learn physics live with RG Sir at RG Lectures

The MHTCET 2027 Long Term Batch covers MHT-CET Physics and Chemistry with live classes, recordings, and Class 11 Physics basics.
Explore the batch

Frequently asked questions

Only the load part of the primary current is cancelled. The magnetising current sets up the core flux and has no counterpart in the secondary, so net flux stays at the value the supply voltage demands. Leakage flux also stops the cancellation being perfect.
The primary carries only the small magnetising current, just enough to set up the core flux that matches the supply voltage. With no secondary current there is no load component, so the primary draws far less than it does under load.
No. Real transformers lose power as heat, so efficiency stays below 100%, roughly 98 to 99% for typical distribution units.
A steady direct current produces a steady flux, and Faraday's law needs changing flux to induce a voltage. With no change in flux, the secondary gets no EMF after the first instant of switching on.

For a sinusoidal supply, the RMS EMF in a winding is Erms ≈ 4.44 f N A Bpeak, with f the frequency, N the turns, A the core cross-section and Bpeak the peak flux density (Wikipedia, Transformer). Since A·Bpeak is the peak flux Φm, this is E = 4.44 f N Φm.

Sources

  1. 1.OpenStax College Physics, 23.7 Transformers, OpenStax, Rice University, 2012
  2. 2.Wikipedia, Transformer, Wikipedia
  3. 3.Star Rating List for Distribution Transformer, Bureau of Energy Efficiency, as hosted on keralaenergy.gov.in, 14 September 2015